Setting up the delivery of SONARPLEX events as northbound SNMP Traps for integration into 3rd party software like alert consoles or other monitoring tools.
The instructions are based on the following example setup. Only events of type NOTIFICATION and no SOFT state events should be sent.
This is the device that should send events northbound to the Trap Receiver.
Location | Cologne |
IP-Address | 172.16.0.100 |
IP-Address | 172.16.10.254 |
SNMP UDP Port | 162 |
SNMP Community | How-ToSNMPTraps |
The backup receiver.
IP-Address | 192.168.100.254 |
SNMP UDP Port | 8000 |
Enable the SNMP trap delivery on the Sender.
Parameter | Setting |
---|---|
Deliver following events as Traps | Service Notifications Host Notifications Admin Notifications Acknowledgements Suppress SOFT state alerts |
Trap Destinations(s) | 172.16.10.254:161, 192.168.100.254:8000 |
Trap Community String | How-ToSNMPTraps |
Debug Level | WARN |
Ideally import the AZETI-TRAP-MIB into the receiving software if you require OID translation.
The MIB file can be downloaded in the administrative web interface of the sending SONARPLEX device, choose System :: MIBs and click on AZETI-TRAP-MIB.txt to download it.